This topic describes the concepts involved in setting up an EtherNet/IP I/O connection. For step-by-step procedures for Allen-Bradley, Omron, or Schneider Electric PLCs, see the Using Allen-Bradley Controllers via EtherNet/IP I/O, Using Omron Controllers via EtherNet/IP I/O, and Using Schneider Electric PLCs via EtherNet/IP I/O topics. For details on controlling the RMC once a connection has been made, see the Using an EtherNet/IP I/O Connection topic.

Setting up an EtherNet/IP I/O connection involves the following concepts:

The version Lexium MDrive Ethernet Application used will be determined by the model/version, The.zip file includes all available upgrade files. The version number can be viewed on the lower-right of the TCP/IP Configuration Utility screen. Download includes Profinet GDS and EIP EDS files. Check the release version prior to performing an upgrade. Electronic Data Sheets (EDS) Use EDS files with network configuration tools to help you identify products and easily commission them on a network. Use our Product Compatibility Download Center or our EPS library to search for the EDS files. Explore the EDS library Search PCDC for EDS files. EtherNet/IP EDS Files for Tool Changers: Part Number File; 9121-DKD-M: 90.eds: 9121-DKF-M: 90.eds: 9121-DKG-M: 90.eds: 9121-DKK-M: 9031.

Using the Correct EDS File

Electronic Data Sheet files (EDS files) are used by many vendors' EtherNet/IP configuration tools to help configure the communications. For configuration tools that do not use EDS files to configure EtherNet/IP I/O connections, see Using a Generic EDS below.

Several EDS files are available for the RMC controllers. EDS files are included when installing RMCTools to your computer. Current versions of EDS files are also available for download from Delta’s website www.deltamotion.com. Each EDS file is packaged in a compressed (.zip) file with its corresponding icon.

From the following table, choose the correct EDS file for your RMC and RMC firmware version:

Product

RMC Firmware

EDS File

Version1

Download Location

RMC75E

2.20-3.40.x

rmc75e_v1.eds

1.x

3.41.0-3.61.x

rmc75e_v2.eds

2.1

3.62.0 or newer

rmc75e_v3.eds

3.1

RMC150E

2.20-3.40.x

rmc150e_v1.eds

1.x

3.41.0-3.61.x

rmc150e_v2.eds

2.1

3.62.0 or newer

rmc150e_v3.eds

3.1

RMC200 CPU20L

1.14.0 or newer

r200-cpu20L_v1.eds

1.1

RMC200 CPU40

1.06.0 or newer

r200-cpu40_v1.eds

1.1

1This revision refers to the EtherNet/IP Identity Object revision, not the firmware revision. This revision only changes when the EtherNet/IP functionality is changed.

Once the correct EDS compressed file has been downloaded, extract the EDS file and icon to a temporary folder and import them into your EtherNet/IP configuration tool.

The correct EDS file is also embedded in the RMC controller itself and may be uploaded into the EtherNet/IP configuration tool, if supported by that particular tool. The steps required for this are tool-specific. Embedded EDS files are not supported by RMC75/150 firmware 3.40.x or older.

Connection Type

The RMC supports three types of I/O connections:

  • Input/Output
    This connection is bidirectional: the originator (PLC or HMI) produces data consumed by the RMC and the target (RMC) produces data that is consumed by the originator. This connection type is also called an Exclusive Owner connection or the controlling connection.

  • Input Only
    For this connection type, only the target (RMC) produces data, which is consumed by the originator (PLC or HMI). The originator will only send a heartbeat packet, sometimes at a reduced interval (less frequently than the RPI) used to allow the RMC to identify when the connection is broken.

  • Listen Only
    This connection type is identical to an Input Only connection type, with one exception: a Listen Only connection can only exist when one of the other I/O connection types has been established. That is, a Listen Only connection cannot be established until an Input/Output or Input Only connection has been established, and conversely when the last non-Listen-Only connection has been closed or has timed out, the Listen Only connection will automatically close as well. This connection type is the least-frequently used. This connection type is not supported by RMC75/150 firmware 3.40.x or older.

Of these three, the Input/Output connection type is by far the most commonly used. The other two are generally only used when multiple I/O connections are used. See the Multiple EtherNet/IP I/O Connections topic for details.

Max Number of Connections and Data

Connection Type

RMC75E

RMC150E

RMC200

Total I/O Connections

4

4

4

Input/Output Connections

1

1

up to 3

Input Only Connections

up to 4

up to 4

up to 4

Listen Only Connections

up to 4

up to 4

up to 4

Connection#1 Size

125 input registers

124 output registers

125 input registers

124 output registers

360 input registers

360 output registers

Connection#2 Size

n/a

n/a

125 input registers

124 output registers

Connection#3 Size

n/a

n/a

125 input registers

124 output registers

When using the RMC’s EDS file in your EtherNet/IP configuration tool, you should be able to select the I/O connection type from a list. Notice that in addition to the three listed above, you may also see Input/Output with Config and Input Only with Config. These connection types are generally not used. If you are using a Generic EDS File (as required by RSLogix 5000 prior to version 20), see the Using a Generic EDS File section below.

Since the RMC200 supports 3 I/O connections, it is possible for several PLCs to communicate with the RMC at once, each with a controlling connection. This is not possible to for the RMC75 and RMC150, as they support only one I/O connection.

Requested Packet Interval (RPI)

EtherNet/IP I/O sends data between the communicating devices at the Requested Packet Interval (RPI). The RPI is configured in the EtherNet/IP controller (for example, RSLogix 5000), not in RMCTools. The RMC supports the following RPIs, based on the number of simultaneous I/O connections established (see the Multiple EtherNet/IP I/O Connections topic):

I/O Connections

Minimum RPI
RMC75/150

Minimum RPI
RMC200 CPU20L

Minimum RPI
RMC200 CPU40

Typical RPI

Maximum RPI

1 (typical)

2 ms

1ms*

1ms

20 ms

10,000 ms

2

3 ms

3

4 ms

4

4 ms

*Not all CPU20L connections can be 1 ms. The CPU20L supports a bandwidth of 6000 packets per second and the CPU40 supports 8000 packets per second. The bandwidth of each connection is calculated as ( 2 / RPI ). For example, an RPI of 1 ms is 2/0.001 = 2000 packet/sec. The CPU20L can support 3 connections at 1 ms RPI.

The RPI must be both an integer number of milliseconds and a multiple of the RMC’s Loop Time. For example, an RPI of 9 ms would not be allowed for a loop time of 2 ms or 4 ms, but would be for 1 ms or lower loop times.

Delta recommends using the slowest RPI that meets the requirements of your application in order to reduce network requirements. See the EtherNet/IP I/O Performance topic for more details.

Multicast vs. Point-to-Point (Unicast)

The RMC supports both multicast and unicast (point-to-point) I/O connections. In almost all cases, unicast I/O connections should be selected whenever supported by the EtherNet/IP I/O controller, in order to reduce network traffic.

The RMC75/150 require multicast I/O connections only when multiple I/O connections will be established at once, which is quite rare. The RMC200 allows multiple unicast I/O connections.

Input Data

The Input Data is the data produced by the RMC and sent to the PLC. By default, the source of the Input Data is the Indirect Data Map, beginning with Indirect Data Map item 0. First, you must set up the Indirect Data Map in RMCTools to map to the RMC registers you want to transfer. Typically, you would include Actual Positions, Status and Error Bits for each axis of control, task status registers so the PLC can tell which user programs are running, and any other registers of your choice. The Input Data source can be changed to something other than the Indirect Data Map, as described below, but the Indirect Data Map is used in nearly all EtherNet/IP I/O applications.

The size of the Input Data is specified in the PLC when configuring the EtherNet/IP I/O connection. This should be set to the number of registers you have set up in the Indirect Data Map, plus the Sync Register, if used. For details on the Sync Register, see the Using an EtherNet/IP I/O Connection topic.

Once an EtherNet/IP I/O connection is established, the Input Data will automatically be sent from the RMC to the PLC each RPI. The PLC can use the data whenever it needs it.

Eds Files Schneider

Setting the Input Data Source in RMCTools

To set the source in the RMC for the Input Data:

  1. In the Project pane, expand the Modules folder, double-click the CPU module, and choose EtherNet/IP.

  2. Under I/O Connection Settings, in the Outgoing Data box, use the browse button to use the Address Selection Tool to find the location you want to use.

  3. If using multiple connections, repeat for the other connections.

Notice that the length of the Input Data is specified in the PLC, not in RMCTools.

Output Data

The Output Data is the data sent from the PLC and consumed by the RMC. By default, the destination of the Output Data is the Indirect Data Map. This allows the PLC to easily write to whatever registers you have mapped into the Indirect Data Map, such as variables and axis command registers. The destination of the Output Data can be changed to something other than the Indirect Data Map registers, as described below. However, the Indirect Data Map works very well for most applications.

The size of the Output Data is specified in the PLC when configuring the EtherNet/IP I/O connection. The Output Data size must be the number of registers you wish to write, plus the Sync Register, if used. For details on the Sync Register, see the Using an EtherNet/IP I/O Connection topic.

Once an EtherNet/IP I/O connection is established, the Output Data is used to write to the RMC. Refer to the Using an EtherNet/IP I/O Connection topic for details.

Setting the Output Data Destination in RMCTools

To set the destination in the RMC for the Output Data:

  1. In the Project pane, expand the Modules folder, double-click the CPU module, and choose EtherNet/IP.

  2. Under I/O Connection Settings, in the Incoming Data box, use the browse button to use the Address Selection Tool to find the location you want to use.

  3. If using multiple connections, repeat for the other connections.

Notice that the length of the Output Data is specified in the PLC, not in RMCTools.

Using a Generic EDS File

Some PLC EtherNet/IP configuration tools do not support importing third-party EDS files. In these cases, additional connection configuration information usually must be entered into a generic device template. The following charts provides the correct values for various connection settings that may be required by your EtherNet/IP configuration tool:

RMC75/150 Connections:

Setting

Connection Type

Input/Output

Input Only

Listen Only

Input Connection Point1,2

1

Output Connection Point1,2

2

32

33

Config Data Assembly Instance2

4

Connection Path2

20 04 24 04 2C 02 2C 01

20 04 24 04 2C 20 2C 01

20 04 24 04 2C 21 2C 01

Transport Class

13

Trigger Type

Cyclic3

O->T Format

32-bit Run/Idle3

Heartbeat

O->T Fixed/Variable

Fixed3

O->T Connection Type

Point-to-point3

O->T Priority

Scheduled3

O->T Size

4, 8, …, 496 bytes

0 bytes

T->O Format

Modeless3

T->O Fixed/Variable

Fixed3

T->O Connection Type

Point-to-point or Multicast

T->O Priority

Scheduled3

T->O Size

4, 8, …, 500 bytes

O->T RPI

2ms to 10000ms

T->O RPI

2ms to 10000ms

Configuration Data Size

0 bytes

RMC200 Input/Output Connections:

Setting

Input/Output Connection #1

Input/Output Connection #2

Input/Output Connection #3

Input Connection Point1,2

1

5

7

Output Connection Point1,2

2

6

8

Config Data Assembly Instance2

4

4

4

Connection Path2

20 04 24 04 2C 02 2C 01

20 04 24 04 2C 06 2C 05

20 04 24 04 2C 08 2C 07

Transport Class

13

Trigger Type

Cyclic3

O->T Format

32-bit Run/Idle3

O->T Fixed/Variable

Fixed3

O->T Connection Type

Point-to-point3

O->T Priority

Scheduled3

O->T Size

4, 8, …, 1440 bytes

4, 8, …, 496 bytes

4, 8, …, 496 bytes

T->O Format

Modeless3

T->O Fixed/Variable

Fixed3

T->O Connection Type

Point-to-point or Multicast

T->O Priority

Scheduled3

T->O Size

4, 8, …, 1440 bytes

4, 8, …, 500 bytes

4, 8, …, 500 bytes

O->T RPI

1ms to 10000ms

T->O RPI

1ms to 10000ms

Configuration Data Size

0 bytes

RMC200 Input Only Connections:

Setting

Input Only

Connection #1

Input Only

Connection #2

Input Only

Connection #3

Input Connection Point1,2

1

5

7

Output Connection Point1,2

32

32

32

Config Data Assembly Instance2

4

4

4

Connection Path2

20 04 24 04 2C 20 2C 01

20 04 24 04 2C 20 2C 05

20 04 24 04 2C 20 2C 07

Transport Class

13

Trigger Type

Cyclic3

O->T Format

Heartbeat

O->T Fixed/Variable

Fixed3

O->T Connection Type

Point-to-point3

O->T Priority

Scheduled3

O->T Size

0 bytes

T->O Format

Modeless3

T->O Fixed/Variable

Fixed3

T->O Connection Type

Point-to-point or Multicast

T->O Priority

Scheduled3

T->O Size

4, 8, …, 1440 bytes

4, 8, …, 500 bytes

4, 8, …, 500 bytes

O->T RPI

1ms to 10000ms

T->O RPI

1ms to 10000ms

Configuration Data Size

0 bytes

RMC200 Listen Only Connections:

Setting

Listen Only

Connection #1

Listen Only

Connection #2

Listen Only

Connection #3

Input Connection Point1,2

1

5

7

Output Connection Point1,2

33

33

33

Config Data Assembly Instance2

4

4

4

Connection Path2

20 04 24 04 2C 21 2C 01

20 04 24 04 2C 21 2C 05

20 04 24 04 2C 21 2C 07

Transport Class

13

Trigger Type

Cyclic3

O->T Format

Heartbeat

O->T Fixed/Variable

Fixed3

O->T Connection Type

Point-to-point3

O->T Priority

Scheduled3

O->T Size

0 bytes

T->O Format

Modeless3

T->O Fixed/Variable

Fixed3

T->O Connection Type

Multicast

T->O Priority

Scheduled3

T->O Size

4, 8, …, 1440 bytes

4, 8, …, 500 bytes

4, 8, …, 500 bytes

O->T RPI

1ms to 10000ms

T->O RPI

1ms to 10000ms

Configuration Data Size

0 bytes

1 The term ‘Assembly Instance’ is used by some applications instead of ‘Connection Point’.

Eds FilesEds files not registering

2 The Input and Output Connection Points and Config Data Assembly Instance are implied by the Connection Path. Therefore, configuration tools will generally either ask for the Connection Points and Instances or the Connection Path but not both.

3 This value is the common default value for this setting and the option to change this field may not be offered by the configuration tool.

Unfortunately which fields are required and how they are presented varies significantly from one tool to the next. For this reason, most EtherNet/IP configuration tools are moving toward supporting importing EDS files to reduce the complexity of setting up an I/O connection.

Advanced Multicast Settings

In addition to the standard settings described above, the RMC provides advanced multicast I/O connection settings. These include the ability to override the default multicast address and Time To Live (TTL) value. See the EtherNet/IP Settings Page topic for details on these settings.

See Also

EtherNet/IP Overview | Using an EtherNet/IP I/O Connection | Using Allen-Bradley Controllers via EtherNet/IP I/O | Using Omron Controllers via EtherNet/IP I/O

Copyright (c) 2005-2020 by Delta Computer Systems, Inc.

CANopen for Inverter Option with Firmware 3101 and earlier

Inverter Option SI-S3 & SI-S3/V: EDS file for U1000, GA700, GA500, A1000, V1000, L1000A, L1000V, T1000A & T1000V Option with Firmware 3101 and earlier

CANopen for Inverter Option with Firmware 3102

Inverter Option SI-S3 & SI-E3/V: EDS file for U1000, GA700, GA500, A1000, V1000, L1000A, L1000V, T1000A & T1000V Option with Firmware 3102

CANopen for Inverter Option with Firmware 3103

Inverter Option SI-S3 & SI-E3/V: EDS file for U1000, GA700, GA500, A1000, V1000, L1000A, L1000V, T1000A & T1000V Option with Firmware 3103

CANopen for Servo

CANopen for XtraDrive

DeviceNet for Inverter (SI-N3)

DeviceNet for Inverter (SI-N3/V)

DeviceNet for Servo (NS300)

DeviceNet for Servo (NS300E)

DeviceNet for Servo (OCA04A)

DeviceNet for Servo (OCA05A)

EtherCAT for Inverter (EUOP-SI-ES3 / EUOP-SI-ES3/V)

Communication option card for A1000, V1000, T1000A/V inverter drives

EtherCAT for Inverter (SI-ES3 / SI-ES3/V)

Communication option card for all 1000-Series drives, GA700, GA500 and regenerative units

EtherCAT for Servo (E1 CoE)

EtherCAT for Sigma-7 Servo 200V (single axis) rev.8.14

EtherCAT for Sigma-7 Servo 400V (double axis) rev.8.14

EtherCAT for Sigma-7 Servo 400V (single axis) rev.8.14

Servo Option SGD7S-xxxDA0xxxxF64 400V CoE rev.8.14

EtherNet/IP for Inverter (SI-EN3Dv) V2.03

Inverter Option SI-EN3D & SI-EN3D/V EtherNet/IP Dualport: EDS Files (Version 2.03) for GA700, A1000, U1000, V1000, T1000A & T1000V Option with Firmware 0342

EtherNet/IP for Inverter (SI-EN3Dv) V2.04

Inverter Option SI-EN3D & SI-EN3D/V EtherNet/IP Dualport: EDS Files (Version 2.04) for GA700, A1000, U1000, V1000, T1000A & T1000V Option with Firmware 0343

EtherNet/IP for Inverter (SI-EN3Dv) V2.05

Inverter Option SI-EN3D & SI-EN3D/V EtherNet/IP Dualport: EDS Files (Version 2.05) for GA700, A1000, U1000, V1000, T1000A & T1000V Option with Firmware 0344

EtherNet/IP for Inverter (SI-EN3Dv) V2.06

Inverter Option SI-EN3D & SI-EN3D/V EtherNet/IP Dualport: EDS Files (Version 2.06) for GA700, GA500, A1000, U1000, V1000, T1000A & T1000V Option with Firmware 0345

EtherNet/IP for Inverter (SI-EN3v) Vers. 1.01

Inverter Option SI-EN3 & SI-EN3/V: EDS Files (Version 1.01) for A1000, V1000, T1000A & T1000V Option with Firmware 0221 (April 2014)

EtherNet/IP for Inverter (SI-EN3v) Vers. 1.06

Inverter Option SI-EN3 & SI-EN3/V: EDS Files (Version 1.06) for A1000, V1000, U1000, T1000A & T1000V Option with Firmware 4101 (June 2015)

EtherNet/IP for Inverter (SI-EN3v) Vers. 1.07

Inverter Option SI-EN3 & SI-EN3/V: EDS Files (Version 1.07) for A1000, V1000, U1000, T1000A & T1000V Option with Firmware 4102 (June 2016)

EtherNet/IP for Inverter (SI-EN3v) Vers. 1.08

Inverter Option SI-EN3 & SI-EN3/V: EDS Files (Version 1.08) for GA700, GA500, A1000, V1000, D1000, R1000, U1000, T1000A, Option with Firmware 4103 (July 2019)

POWERLINK for Inverter (SI-EL3v)

Inverter Option SI-EL3 & SI-EL3/V: XDD files for A1000, V1000

POWERLINK for Servo (OCB02A Vers. 3.xx)

For Sigma-5 Servo Option SGDV-OCB02A (supporting B&R Automation Studio 3.xx)

POWERLINK for Servo (OCB02A Vers. 4.xx)

For Sigma-5 Servo Option SGDV-OCB02A (supporting B&R Automation Studio 4.xx)

PROFIBUS for Inverter (SI-P3)

Inverter Option SI-P3 & SI-P3/V: GSD Files for A1000, V1000, T1000A & T1000V

PROFIBUS for Servo (NS500)

PROFIBUS for Servo (NS500E)

Eds Files For Rslinx

PROFIBUS for XtraDrive

PROFINET for Inverter (SI-EP3)

Eds Files Database

Inverter Option SI-EP3 & SI-EP3/V: GSDML Files for A1000, V1000, T1000A & T1000V

PROFINET for Servo (CM2307-E)

PROFINET for Servo (OCB03A)

PROFINET for Servo (Sigma-7 200V)

PROFINET for Servo (Sigma-7 400V)